On an isolated or compensated MV feeder, a single-phase ground fault can draw only a few amps. The feeder stays up, so nothing looks urgent, but the insulation at the fault point is under continuous stress. Overcurrent relays rarely pick this up reliably. A small-current ground fault locating unit is meant to fill that gap. It gives the DTU or FTU a direction or a section number it can act on.

The FTU is installed on a pole switch or sectionalizer. The DTU is installed at a ring main unit or switching station and monitors several bays. Both devices are aware of the switch position and can communicate with the master station or between themselves. One of the things they need is a reliable ground-fault criterion. The location device measures the zero-sequence voltage and current at its site and implements a directional or sectional algorithm. It doesn't trip normally. It sends the finding to the DTU/FTU. The terminal compares that finding with its switch position, local current direction, and other terminal statuses, and then makes a decision to open, block close or just notify about the section.
In a resonant-grounded network, one common method is harmonic injection. The arc-suppression coil is briefly blocked during the fault, and third-harmonic current is injected. FTUs and DTUs along the feeder compare third-harmonic zero-sequence current. It appears on the fault path and is weak on healthy sections. The terminal that sees the step change marks the boundary. The locating function handles the injection trigger and the criterion; the terminal provides the measurement and the report.
Transient methods are used the same way. In a resonant-grounded system, transient zero-sequence current or transient admittance carries direction information that holds up better on high-resistance faults than steady-state magnitude. An FTU can extract that feature locally and make a section decision, or send it to a peer across a sectionalizing point. The locating unit's job is a stable sampling front end and a proven algorithm. The FTU's job is the switch and the peer coordination.
Speed matters. If terminals exchange direction results over IEC 61850 GOOSE, the decision can stay local and happen in milliseconds. A temporary fault may not last long enough for a master-station poll. With a distributed scheme, the locating unit and the DTU/FTU swap a few priority messages: fault seen, direction, permit or block. With a centralized scheme, the same data goes up with time stamps and the master station works out the section from topology.
Timing is the usual weak point. FTUs and DTUs do not sample or report with the same timing behavior. If time alignment is poor, the master station can build the wrong sequence even when each terminal reports a reasonable direction. A locating scheme that compares features across terminals needs a common time reference, or it should be reduced to a local single-terminal criterion. This is one reason transient-admittance and harmonic-content methods are often chosen over schemes that need tight synchronization across many nodes.

When you specify the system, match the algorithm to the grounding method: resonant, isolated or resistance-grounded. Set the DTU/FTU to pass through the locating result instead of re-checking it against an overcurrent setting that was never designed for small ground current. The result should be a section indication at the terminal that can isolate it, not a general alarm that sends a crew to walk the whole feeder.